Lubemast oil cleaning at work
Case Study

Cleaning Transformer Oil

Good results cleaning transformer oil with the Lubemaster OS600 at a Paper Mill. 

Approximately 100 litres of waste Shell Diala M transformer oil was decanted into the Lubemaster.  An initial sample of the oil was taken and testing showed the following results:

First Test Results

Water % of Saturation 70%
Dielectric Strength 5kV
-Particle Count
15um 254.2
25um 64.2
50um 7.7
100um 9.0

Test Results Post-Cleaning

Water % of Saturation20% – DOWN 48%
Dielectric Strength60kV – INCREASE OF 55kV
-Particle Count 
 15um121.7
 25um25.7
 50um1.9
100um0.3

Results

The Lubemaster filtered the oil for approximately 8 hours at 40degC with pump pressure of 60psi and vacuum -7.  At this time a second oil sample was taken and tested.  The tests showed the following results.